JUT1-16 series ( DIN rail mounted screw terminal blocks Screw Cage Terminal Blocks)

The screw-type industrial terminal block has strong static connection stability, high versatility, and can be quickly installed on U-shaped guide rails and G-shaped guide rails. Abundant and practical accessories. Traditional and reliable. Working current: 76 A, Operating Voltage: 800V. Wiring method: screw connection. Rated wiring capacity: 16 mm2 Installation method: NS 35/7.5, NS 35/15NS32.

Products Details

Advantage of JUT1-16 Series

Universal mounting foot, available for rails NS35 and NS32.

Static connection stability is strong.

Potential distribution with bridges.

Note: When aligned with the same size feed-through terminals, an end plate must be inserted to isolate voltages greater than 690 V.

JUT1-16 Series

Product number JUT1-16 JUT1-16PE
product type Rail Terminals Rail ground terminal
Mechanical structure screw type screw type
layers 1 1
Electric potential 1 1
connection volume 2 2
Rated cross section 16 mm2 16 mm2
Rated current 76A
Rated voltage 800V
open side panel Yes no
grounding feet no Yes
other
Application field Widely used in electrical connection, industrial Widely used in electrical connection, industrial
color gray, customizable yellow and green

Wiring Data

Line contact
Stripping length 11mm 11mm
Rigid Conductor Cross Section 2.5mm² — 25mm² 2.5mm² — 25mm²
Flexible conductor cross section 4mm² — 16mm² 4mm² — 16mm²
Rigid Conductor Cross Section AWG 14-4 12-4
Flexible Conductor Cross Section AWG 12-6 12-6

Size

thickness 12.2mm 12.2mm
width 42.5mm 42.5mm
high
NS35/7.5 high 54mm 54mm
NS35/15 high 61.5mm 61.5mm
NS15/5.5 high

Material Properties

Flame retardant grade, in line with UL94 V0 V0
Insulation Materials PA PA
Insulation material group I I

IEC Electrical Parameters

standard test IEC 60947-7-1 IEC 60947-7-2
Rated voltage(III/3) 800V
Rated current(III/3) 76A
Rated surge voltage 8kv 8kv
Overvoltage class III III
pollution level 3 3

Electrical Performance Test

Surge Voltage Test Results Passed the test Passed the test
Power frequency withstand voltage test results Passed the test Passed the test
Temperature rise test results Passed the test Passed the test

Environmental Conditions

Surge Voltage Test Results -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.)
Ambient temperature (storage/transport) -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C)
Ambient temperature (assembled) -5 °C — 70 °C -5 °C — 70 °C
Ambient temperature (execution) -5 °C — 70 °C -5 °C — 70 °C
Relative Humidity (Storage/Transportation) 30 % — 70 % 30 % — 70 %

Environmental Friendly

RoHS No excessive harmful substances No excessive harmful substances

Standards and Specifications

Connections are standard IEC 60947-7-1 IEC 60947-7-2

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours