Advantage of JUT1-16 Series
Universal mounting foot, available for rails NS35 and NS32.
Static connection stability is strong.
Potential distribution with bridges.
Note: When aligned with the same size feed-through terminals, an end plate must be inserted to isolate voltages greater than 690 V.
JUT1-16 Series
| Product number | JUT1-16 | JUT1-16PE | 
| product type | Rail Terminals | Rail ground terminal | 
| Mechanical structure | screw type | screw type | 
| layers | 1 | 1 | 
| Electric potential | 1 | 1 | 
| connection volume | 2 | 2 | 
| Rated cross section | 16 mm2 | 16 mm2 | 
| Rated current | 76A | |
| Rated voltage | 800V | |
| open side panel | Yes | no | 
| grounding feet | no | Yes | 
| other | ||
| Application field | Widely used in electrical connection, industrial | Widely used in electrical connection, industrial | 
| color | gray, customizable | yellow and green | 
Wiring Data
| Line contact | ||
| Stripping length | 11mm | 11mm | 
| Rigid Conductor Cross Section | 2.5mm² — 25mm² | 2.5mm² — 25mm² | 
| Flexible conductor cross section | 4mm² — 16mm² | 4mm² — 16mm² | 
| Rigid Conductor Cross Section AWG | 14-4 | 12-4 | 
| Flexible Conductor Cross Section AWG | 12-6 | 12-6 | 
Size
| thickness | 12.2mm | 12.2mm | 
| width | 42.5mm | 42.5mm | 
| high | ||
| NS35/7.5 high | 54mm | 54mm | 
| NS35/15 high | 61.5mm | 61.5mm | 
| NS15/5.5 high | 
Material Properties
| Flame retardant grade, in line with UL94 | V0 | V0 | 
| Insulation Materials | PA | PA | 
| Insulation material group | I | I | 
IEC Electrical Parameters
| standard test | IEC 60947-7-1 | IEC 60947-7-2 | 
| Rated voltage(III/3) | 800V | |
| Rated current(III/3) | 76A | |
| Rated surge voltage | 8kv | 8kv | 
| Overvoltage class | III | III | 
| pollution level | 3 | 3 | 
Electrical Performance Test
| Surge Voltage Test Results | Passed the test | Passed the test | 
| Power frequency withstand voltage test results | Passed the test | Passed the test | 
| Temperature rise test results | Passed the test | Passed the test | 
Environmental Conditions
| Surge Voltage Test Results | -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) | -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) | 
| Ambient temperature (storage/transport) | -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) | -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) | 
| Ambient temperature (assembled) | -5 °C — 70 °C | -5 °C — 70 °C | 
| Ambient temperature (execution) | -5 °C — 70 °C | -5 °C — 70 °C | 
| Relative Humidity (Storage/Transportation) | 30 % — 70 % | 30 % — 70 % | 
Environmental Friendly
| RoHS | No excessive harmful substances | No excessive harmful substances | 
Standards and Specifications