JUT1-4 series (Right Angle Screw Terminal Universal Installation Panel Mounted Feed Through Screw Cage Din Rail Electric wire connectors)

The screw-type industrial terminal block has strong static connection stability, high versatility, and can be quickly installed on U-shaped guide rails and G-shaped guide rails. Abundant and practical accessories. Traditional and reliable. Working current: 32 A, Operating Voltage: 800V. Wiring method: screw connection. Rated wiring capacity: 4 mm2 Installation method: NS 35/7.5, NS 35/15, NS32.

Products Details

Universal mounting foot, available for rails NS35 and NS32. Static connection stability is strong. Potential distribution with bridges.
Product number JUT1-4 JUT1-4PE JUT1-4/2 JUT1-4/2L JUT1-4/1-2 JUT1-4/2-2 JUT1-4/2Q Product number JUT1-4/1-2PE JUT1-4/2-2PE JUT1-4E JUT1-4E/PE JUT1-4K JUT1-4K/2-2 JUT1-4RD
product type Rail Terminals Rail ground terminal Double-layer rail terminal block Double layer connecting rail terminal block One-in-two-out rail terminal block Two-in-two-out rail terminal block Double Layer Bridgeable Rail Terminal Blocks product type One-in-two-out rail grounding terminal Two-in-two-out rail grounding terminal Miniature Rail Ground Terminals Miniature Rail Ground Terminals Knife switch disconnecting rail terminal Two-in, two-out knife switch disconnecting rail terminal Fuse Rail Terminal Blocks
Mechanical structure screw type screw type screw type screw type screw type screw type screw type Mechanical structure screw type screw type screw type screw type screw type screw type screw type
layers 1 1 2 2 1 1 2 layers 1 1 1 1 1 1 1
Electric potential 1 1 2 2 1 1 2 Electric potential 1 1 1 1 1 1 1
connection volume 2 2 4 4 3 4 4 connection volume 3 4 2 2 2 4 2
Rated cross section 4 mm2 4 mm2 4mm2 4mm2 4mm2 4mm2 4mm2 Rated cross section 4 mm2 4 mm2 4mm2 4mm2 4mm2 4mm2 4mm2
Rated current 32A 32A 32A 32A 32A 32A Rated current 32A 16A 16A 6.3A
Rated voltage 800V 500V 800V 500V 630V 500V Rated voltage 500V 500V 630V 800V
open side panel Yes no no no no no no open side panel no no Yes no no Yes no
grounding feet no Yes no no no no no grounding feet Yes Yes no Yes no no no
other When aligned with terminals of the same size, an end plate must be inserted to isolate voltages greater than 690 V。 Upper and lower layers are turned on Multi-conductor Bridgeable up and down other G/5x20 fuse
Application field Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial Application field Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial Widely used in electrical connection, industrial
color gray、customizable yellow and green 灰gray、customizable gray、customizable gray、customizable gray、customizable gray、customizable color yellow and green yellow and green gray、customizable yellow and green gray、customizable gray、customizable gray、customizable
Line contact
Stripping length 8mm 8mm 8mm 8mm 8mm 8mm 8mm 8mm 8mm 8mm 8mm 8mm 8mm 8mm
Rigid Conductor Cross Section 0.2mm² — 4mm² 0.2mm² — 6mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 6mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 6mm² 0.2mm² — 6mm² 0.2mm² — 6mm² 0.2mm² — 6mm² 0.2mm² — 6mm² 0.2mm² — 4mm²
Flexible conductor cross section 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm² 0.2mm² — 4mm²
Rigid Conductor Cross Section AWG 24-12 24-10 24-12 24-12 24-12 24-10 24-12 24-12 24-10 24-10 24-10 24-10 24-10 26-10
Flexible Conductor Cross Section AWG 24-12 24-12 24-12 24-12 24-12 24-12 24-12 24-12 24-12 24-12 24-12 24-12 24-12 26-10
Thickness 6.2mm 6.2mm 6.2mm 6.2mm 6.2mm 6.2mm 6.2mm 6.2mm 6.2mm 6.2mm 6.2mm 6.2mm 6.2mm 8.2mm
Width 42.5mm 42.5mm 56mm 56mm 50.5mm 63.5mm 67mm 50.5mm 63.5mm 28mm 28mm 51mm 63.5mm 72.5mm
High
NS35/7.5 high 47mm 47mm 62mm 62mm 47mm 47mm 62mm 47mm 47mm 58.5mm 47mm 56.5mm
NS35/15 high 54.5mm 54.5mm 69.5mm 69.5mm 54.5mm 54.5mm 69mm 54.5mm 54.5mm 66mm 54.5mm 64mm
NS15/5.5 high 32mm 32mm
Flame retardant grade, in line with UL94 V0 V0 V0 V0 V2 V2 V0 V2 V2 V0 V0 V2 V2 V0
Insulation Materials PA
Insulation material group I
Standard test IEC 60947-7-1 IEC 60947-7-2 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-2 IEC 60947-7-2 IEC 60947-7-1 IEC 60947-7-2 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-3
Rated voltage(III/3) 800V 500V 800V 500V 630V 500V 500V 500V 630V 800V
Rated current(III/3) 32A 32A 32A 32A 32A 32A 32A 16A 16A 6.3A
Rated surge voltage 8kv 8kv 6kv 8kv 6kv 8kv 6kv 8kv 8kv 6kv 6kv 6kv 8kv 6kv
Overvoltage class III
Pollution level 3
Surge Voltage Test Results -60 °C-105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -40 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -40 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -40 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -40 °C - 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.)
Ambient temperature (storage/transport) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -5 °C - 70 °C (short term (up to 24 hours), -60 °C to +70 °C) -5 °C - 70 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -5 °C - 70 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C - 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -5 °C - 70 °C (short term (up to 24 hours), -60 °C to +70 °C)
Ambient temperature (assembled) -5 °C — 70 °C
Ambient temperature (execution) -5 °C — 70 °C
Relative Humidity (Storage/Transportation) 30 % — 70 % 30 % — 70 % 25 % — 75 % 25 % — 75 % 30 % — 70 % 30 % — 70 % 25 % — 75 % 30 % — 70 % 30 % — 70 % 30 % — 75 % 30 % — 75 % 30 % — 70 % 30 % — 70 % 25 % — 75 %
RoHS No excessive harmful substances
Connections are standard IEC 60947-7-1 IEC 60947-7-2 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-2 IEC 60947-7-2 IEC 60947-7-1 IEC 60947-7-2 IEC 60947-7-1 IEC 60947-7-1 IEC 60947-7-3
Surge Voltage Test Results Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test
Power frequency withstand voltage test results Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test
Temperature rise test results Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test Passed the test